EPA Section 608 Technician Certification
EPA 608 Practice Test
This EPA 608 practice test covers all four parts of the Section 608 technician certification test: Core, Type I (small appliances), Type II (high-pressure) and Type III (low-pressure). Each part is 25 questions, the Universal certification takes all four, and the passing score on the closed-book test is 70 percent. The free diagnostic opens when this bank is published.
The free EPA 608 diagnostic is being prepared and is not open yet. The exam facts and the content outline on this page are current.
Section 608 certification is a federal requirement, but the EPA does not give the test. EPA-approved certifying organizations do, and each one sets its own fee, time limit and retake rules. What is the same everywhere is the structure: a 25-question Core section that everyone takes, plus 25 questions for each equipment type you want to be certified for. One type means 50 questions; Universal means 100.
The Core is the part to learn first. It covers what is common to all refrigerant work: ozone depletion, the Clean Air Act and the Montreal Protocol, the Section 608 regulations, and the difference between recovering, recycling and reclaiming refrigerant. The three Type sections then apply those rules to particular equipment, mostly as recovery requirements, leak detection and leak-repair rules.
EPA 608 exam facts: questions, time limit, cost and passing score
What you are preparing for, in the exam owner's own numbers.
| Questions | 100For Universal: Core plus Types I, II and III, 25 questions each. A single type is 50 questions: the Core and that type. |
|---|---|
| Delivery | The EPA does not give the test itself. It is administered by EPA-approved certifying organizations, such as ESCO Institute, Mainstream Engineering Corporation, RSES and many trade schools, as a closed-book proctored test in person or, with some programs, remotely online. Type I alone may also be taken in an open-book mail-in format. Each organization sets its own fee. |
| Eligibility | No prerequisites are stated. Certification is required of technicians who maintain, service, repair or dispose of equipment that could release refrigerants; apprentices are exempt while closely and continually supervised by a certified technician. |
| Passing standard | 70 percent on the closed-book Type I, Type II, Type III and Universal tests, each built from 25 Core questions plus 25 questions for each equipment type; 84 percent for the open-book mail-in Type I format. Universal certification covers all equipment types and needs Core plus Type I, II and III, with the Core taken as a proctored closed-book test. |
| Retakes | EPA sets no retake rule; retakes, waiting periods and fees are decided by the certifying organization. Section 608 credentials do not expire. |
| Outline in force | EPA Section 608 Technician Certification Test Topics (web page last updated December 5, 2025) |
Exam facts are taken from EPA’s own published material, last checked . Source. Confirm fees, dates and rules with the organization you register with before you book.
The four sections. The EPA sets no time limit; your certifying organization does.
| Section | Questions |
|---|---|
| Core | 25 |
| Type I (Small Appliances) | 25 |
| Type II (High-Pressure) | 25 |
| Type III (Low-Pressure) | 25 |
Who takes it
Technicians who maintain, service, repair or dispose of equipment that could release refrigerants. Certification is required for that work; apprentices are exempt while closely and continually supervised by a certified technician. The EPA states no prerequisites for taking the test, and the credential does not expire.
What is on the EPA 608 exam? Domains and weights
Each section is 25 questions, so each is a quarter of the Universal test. The topics under each section are the EPA's published test topics; the EPA does not say how many questions come from each.
| Domain | Weight | What it covers |
|---|---|---|
| CORECore10 tasks | 25% |
All 10 Core tasks
|
| T1Type I (Small Appliances)3 tasks | 25% |
|
| T2Type II (High- and Very High-Pressure)6 tasks | 25% |
All 6 Type II (High- and Very High-Pressure) tasks
|
| T3Type III (Low-Pressure)7 tasks | 25% |
All 7 Type III (Low-Pressure) tasks
|
Key EPA 608 concepts to know
Core: ozone depletion, the Clean Air Act and the Montreal Protocol
- Chlorine is what destroys stratospheric ozone. CFCs such as R-12 have the highest ozone-depletion potential, HCFCs such as R-22 much less, and HFCs such as R-134a have zero because they contain no chlorine.
- Ozone-depletion potential is measured against CFC-11, which is set at 1.0. HCFCs range from about 0.01 to 0.1.
- The Montreal Protocol is the international treaty that phases out production of ozone-depleting substances. US production of CFCs ended at the end of 1995, and production and import of R-22 ended on January 1, 2020.
- The Clean Air Act prohibits knowingly venting refrigerant during service, maintenance, repair or disposal, and the venting ban also applies to substitute refrigerants such as HFCs.
Core: the Section 608 rules, the three Rs and recovery
- Recover means removing refrigerant into an external container without processing it. Recycle means cleaning it for reuse with oil separation and filter-driers. Reclaim means reprocessing it to the AHRI Standard 700 purity standard, confirmed by chemical analysis.
- Self-contained recovery equipment has its own compressor. System-dependent (passive) equipment relies on the appliance's compressor or pressure, and it may not be used on systems holding more than 15 pounds of refrigerant.
- Recovery and recycling equipment must be certified by an EPA-approved third party, and the sales restriction limits who may buy regulated refrigerant.
- Never mix refrigerants in one recovery cylinder. Recovery is faster with higher ambient temperature, larger equipment and shorter, wider hoses.
- There are no drop-in replacements. Match the lubricant to the refrigerant: ester (POE) oils with R-134a, alkylbenzene with HCFCs. Blends fractionate, leaking their components at different rates.
Core: refrigeration cycle, safety and shipping
- Refrigerant leaves the compressor as high-pressure vapor, condenses to liquid in the condenser, drops in pressure through the metering device and absorbs heat as it evaporates in the evaporator. Cooling happens in the evaporator.
- Manifold gauges: blue is the low side (a compound gauge that reads pressure and vacuum), red is the high side, and yellow is the center utility hose.
- Reusable recovery cylinders must be DOT approved and are painted gray with a yellow top. Never fill one beyond 80 percent, and never refill a disposable cylinder.
- Leak test with dry nitrogen through a pressure regulator and relief valve, never oxygen or compressed air, which can explode with oil.
- Refrigerant in an enclosed space displaces oxygen and can cause suffocation, heart problems and frostbite. Evacuate at the end of service to remove air and moisture.
Type I: small appliances
- A small appliance is factory manufactured, charged and hermetically sealed with 5 pounds or less of refrigerant, such as a refrigerator, window air conditioner or water cooler.
- With recovery equipment made after November 15, 1993, recover 90 percent of the charge if the compressor works or 80 percent if it does not, or evacuate to 4 inches of mercury vacuum. Older equipment must recover 80 percent.
- With a passive recovery device, run a working compressor. If it is dead, install access valves on both the high and low sides, and heat and sharply strike the compressor to free trapped refrigerant.
- Remove solderless access fittings when the job is done, because they tend to leak. R-134a is the usual substitute for R-12 in these appliances.
- Refrigerant exposed to an open flame or very high heat breaks down into toxic, corrosive products such as phosgene and acids.
Type II: high- and very high-pressure appliances
- Required evacuation with equipment made after November 15, 1993: 0 inches of mercury for a high-pressure appliance under 200 pounds, and 10 inches for one of 200 pounds or more. Very high-pressure appliances go to 0 inches.
- Leak repair applies to appliances with 50 pounds or more of ozone-depleting refrigerant. Thresholds are 20 percent a year for commercial refrigeration, 30 percent for industrial process refrigeration and 10 percent for comfort cooling and other appliances.
- Leaks over the threshold must be repaired within 30 days, or 120 days if an industrial process shutdown is needed. An appliance leaking 125 percent or more of its full charge in a year must be reported.
- Nitrogen alone is the preferred leak-test gas; nitrogen with a trace of R-22 is next. Signs of a leak include excessive superheat and oil traces.
- Speed recovery by removing liquid first, chilling the recovery cylinder or heating the appliance. Pressure-temperature charts read psig; add 14.7 to convert to psia.
- Never energize a hermetic compressor while the system is under vacuum. ASHRAE Standard 15 requires an oxygen deprivation sensor in equipment rooms.
Type III: low-pressure chillers
- Low-pressure systems run below atmospheric pressure, so leaks pull air in rather than letting refrigerant out. A purge unit removes that air and other noncondensables; excessive purging signals a leak.
- Required evacuation for a low-pressure appliance is 25 mm of mercury absolute. For a non-major repair the system may instead be pressurized to no more than 0 psig before it is opened.
- To pressurize for leak testing, use controlled hot water or a built-in heating device first, and nitrogen second.
- Recover liquid first, then vapor. Heat the oil to 130 degrees F before draining it, and circulate or drain the chiller water during evacuation so the tubes do not freeze.
- When recharging, add vapor before liquid so water in the tubes does not freeze, and charge a centrifugal chiller through the evaporator charging valve. An R-123 equipment room needs a refrigerant sensor.
Common EPA 608 exam mistakes and how to avoid them
Swapping the Type II and Type III evacuation levels
Type II is measured in inches of mercury vacuum (0 or 10 for post-1993 equipment); Type III is 25 mm of mercury absolute. Write both tables on one page and learn them side by side.
Confusing recycle with reclaim
Only reclaimed refrigerant is reprocessed to the AHRI 700 standard and verified by analysis. Recycling is basic cleaning, usually on site.
Picking compressed air or oxygen for leak testing
The answer is always dry nitrogen through a regulator and relief valve; these options are written to tempt candidates who think any dry gas will do.
Applying small appliance percentages to larger equipment
The 90 and 80 percent recovery figures are only for appliances of 5 pounds or less. Larger appliances use vacuum levels instead.
Learning leak rates without the equipment category
Tie each figure to its category: 20 percent commercial refrigeration, 30 percent industrial process, 10 percent comfort cooling, and only at 50 pounds or more.
Studying only your Type and skimming the Core
Every certification includes the Core, and certifying organizations generally require each 25-question section to be passed, so a weak Core can block every type.
How to study for the EPA 608 exam with practice tests
- 1
Decide which certification you need
Type I covers small appliances, Type II high- and very high-pressure appliances and Type III low-pressure appliances. Universal covers all three. Practice the Core plus the sections you will sit.
- 2
Start with Core
Core comes first because every certification includes it, and the Type sections apply its rules to particular equipment.
- 3
Learn the numbers with their reasons
Much of this test is specific figures: evacuation levels, leak rates, dates. Each explanation here gives the rule the number comes from, which is easier to keep than a list.
- 4
Practice each section as a block of 25
Do timed sets of 25 for each section you are taking, then all of your sections back to back. Your certifying organization sets the real time limit, so ask it what you will get.
What is in the paid EPA 608 bank
The question bank
The EPA 608 bank is still being written. The live count appears here when questions are published.
Every option explained
A written reason for every option, right and wrong, plus a one-line takeaway, a cited reference and the outline task the question tests.
Tutor mode and timed mode
Tutor mode shows the explanation after each question. Timed mode holds everything back until the end, at exam pace.
A readiness band, by domain
Your first-attempt results weighted the way the exam weights its domains, shown as a band rather than a pass probability: nobody outside the exam owner knows the cut score.
A study plan
Set your exam date and the plan divides the questions you have not seen across the days you have left, weakest domains first.
How the questions are written and checked
Step 1
Written to the public outline
Each question is written by AI against one task in EPA's published content outline. Nothing is taken from the exam itself.
Step 2
Solved blind by a second model
A different model answers the question without seeing the key. If it does not reach the same answer, the question is not published.
Step 3
Audited for flaws and duplicates
A separate pass looks for item-writing flaws: two defensible answers, a giveaway in the wording, a rationale that contradicts the key. Near-duplicates are removed.
Step 4
Corrected in public
Learners can report any question. Reports and answer statistics flag questions for withdrawal or correction, and every correction is logged.
There is no human subject-matter-expert review in that process, and we do not claim one. What you get instead is a cited reference on every question, so you can check it yourself. Read the full methodology or see the corrections log.
EPA 608 practice test FAQ
How hard is the EPA 608 exam?
The EPA 608 exam is less about reasoning than about knowing exact rules and figures: dates, refrigerant weights, fill limits, evacuation levels and leak rates, each tied to a particular kind of equipment. It is hard if you try to learn the numbers as a list and easier if you learn each one with the rule it belongs to. The EPA publishes no pass rate.
What questions are on the EPA 608 test?
Multiple-choice questions on the topics the EPA publishes for each section: ten for the Core (ozone depletion, the Clean Air Act and Montreal Protocol, the Section 608 rules, recovery, safety and shipping), three for Type I, six for Type II and seven for Type III. Each section is 25 questions, and the EPA does not say how many come from each topic.
How many questions can you miss on EPA 608?
About 7 per 25-question section. The passing score on the closed-book test is 70 percent, and certifying organizations generally apply it to each section separately, which is 18 correct out of 25. We could not confirm the per-section rule in the EPA's own wording, so ask your certifying organization how it scores.
Where can I find an EPA 608 practice test with answers?
Here: every question in this EPA 608 practice exam bank comes with the right answer and the reason each option is right or wrong, tied to the rule it tests. The questions are organized by the EPA's four sections, so you can practice the Core and your type as blocks of 25.
Is there a free practice test for the EPA Universal certification?
Not on this site yet. The free diagnostic, which samples all four Universal sections, opens when this bank is published. The full bank will be on a paid pass, charged once with no renewal.
Are these the real EPA 608 test questions?
No. The EPA 608 practice questions here are original, written to the EPA's published test topics and the current regulation. They are not taken from the EPA test bank or from any certifying organization's test.
EPA Section 608 Technician Certification is a federal certification established under the Clean Air Act and overseen by the U.S. Environmental Protection Agency (EPA). This site is an independent study resource; it is not affiliated with, endorsed by, or approved by the EPA or by any EPA-approved certifying organization, and it does not issue Section 608 certification. Practice questions here are original and are not taken from the EPA test bank.